Advanced Search
    DAN Shijian, WANG Zihao, LIU Youlong, MENG Fanqi, DAN Sike, LIU Zhong. Causes of tube explosion in boiler water wall[J]. PHYSICAL TESTING AND CHEMICAL ANALYSIS PART A:PHYSICAL TESTING, 2022, 58(6): 66-69,74. DOI: 10.11973/lhjy-wl202206017
    Citation: DAN Shijian, WANG Zihao, LIU Youlong, MENG Fanqi, DAN Sike, LIU Zhong. Causes of tube explosion in boiler water wall[J]. PHYSICAL TESTING AND CHEMICAL ANALYSIS PART A:PHYSICAL TESTING, 2022, 58(6): 66-69,74. DOI: 10.11973/lhjy-wl202206017

    Causes of tube explosion in boiler water wall

    • The chemical composition, mechanical properties, metallographic examination and energy spectrum analysis of the drum burst accident of the water wall of a circulating fluidized bed boiler in a power plant were carried out, and the numerical simulation of the failure pipeline was carried out combined with the pipeline and the joint inspection. The results show that the chemical composition and mechanical properties of the failed pipeline met the standard requirements, and there was no obvious abnormality in the metallographic test results. Foreign matter blockage and multiple bulges were found in the inspection of pipeline and joint box. Numerical simulation and strength check were used to confirm that foreign matter blockage was the direct cause of pipe explosion. At the same time, it was found that the local temperature to the fire surface was 550-730 ℃ when the failure pipeline was blocked.
    • loading

    Catalog

      Turn off MathJax
      Article Contents

      /

      DownLoad:  Full-Size Img  PowerPoint
      Return