Advanced Search
    GUO Dan, PENG Zhanghua, ZHANG Weike, ZHAI Guangjie, HE Chengwen, JIANG Hua. Cause of Perforation on Boiler Water Wall Tube in an Own Power Plant[J]. PHYSICAL TESTING AND CHEMICAL ANALYSIS PART A:PHYSICAL TESTING, 2021, 57(3): 73-77. DOI: 10.11973/lhjy-wl202103016
    Citation: GUO Dan, PENG Zhanghua, ZHANG Weike, ZHAI Guangjie, HE Chengwen, JIANG Hua. Cause of Perforation on Boiler Water Wall Tube in an Own Power Plant[J]. PHYSICAL TESTING AND CHEMICAL ANALYSIS PART A:PHYSICAL TESTING, 2021, 57(3): 73-77. DOI: 10.11973/lhjy-wl202103016

    Cause of Perforation on Boiler Water Wall Tube in an Own Power Plant

    • The boiler water wall tube in an industrial park's own power plant perforated for many times during operation. The causes of perforation on water wall tube were analyzed by means of inner wall scale analysis and metallographic examination, combined with the field conditions. The results show that the conductivity and SiO2 content of water in boiler were high, and there was no on-line instrument monitoring in the field, which led to the alkali corrosion under the scale, resulted in the tube wall thinning to unable to bear the stress and the perforation and burst.
    • loading

    Catalog

      Turn off MathJax
      Article Contents

      /

      DownLoad:  Full-Size Img  PowerPoint
      Return