    水表连接黄铜螺母断裂分析

    FRACTURE ANALYSIS OF CONNECTING BRASS NUT FOR TAP WATER METER

    • 摘要: 居民住宅内与水表连接的黄铜螺母发生断裂,造成管路泄漏。采用宏、微观检验方法对失效螺母进行了分析。结果表明,黄铜材料中含有较多的铅,使金属基体脆化并在晶界上存在脆性共晶体网膜,加上金属中还存在孔洞、缩松等铸造缺陷,是造成螺母断裂的主要原因。

       

      Abstract: The fracture of brass nut for connecting tap and water meter lead to pipeline leakage at a residence. The fracture analysis was made by means of macroscopic and scanning electron microscope. Experiment results showed that the fracture of the nut was caused by foundry defects such as holes,shrinkages .And redundant lead in brass nut which formed fragile eutectic omentum in grain boundary was another reason of the fracture.

       

    /