    某330 kV输电线路导线断裂原因

    Reasons for wire breakage in a certain 330 kV transmission line

    • 摘要: 某330 kV输电线路T型线夹处导线发生断裂。采用宏观观察、化学成分分析、尺寸测量、金相检验、拉伸试验及扫描电镜分析等方法研究了导线断裂的原因。结果表明:压接区域变形程度过小,使压接管的压紧力不足,压接管内壁与铝线未充分接触,导致导流面积过小,在运行时导线接触部位温度升高,铝线表面烧灼受损;当线路载荷增大时,导线局部温度进一步升高,抗拉强度大幅下降,最终线夹内部导线被拉断。

       

      Abstract: The wire at the T-shaped clamp of a certain 330 kV transmission line broke. The causes of wire fracture were studied using methods such as macroscopic observation, chemical composition analysis, size measurement, metallographic examination, tensile testing and scanning electron microscopy analysis. The results show that the deformation degree of the crimping area was too small, resulting in insufficient clamping force of the crimping joint. The inner wall of the crimping joint did not fully contact the aluminum wire, so the diversion area was too small. During operation, the temperature of the contact area increased, and the surface of the aluminum wire was burned and damaged. When the load on the line increased, the local temperature of the line further increased, and the tensile strength of the wire decreased significantly, ultimately causd the wire inside the clamp to break.

       

    /